WorkSafeBC minimum approach distances (Table 19-1A)
- Over 750 V to 75 kV: 3 m (10 ft)
- Over 75 kV to 250 kV: 4.5 m (15 ft)
- Over 250 kV to 550 kV: 6 m (20 ft)
These apply to the person and to any tool, machine, material or equipment on the site. Always check the current regulation — the link is below.
When a lift has to get closer
If the distance can't be kept, the regulation requires a written assurance from the owner of the power system before work goes ahead. That can mean the line is moved or rerouted, isolated and grounded, or identified and guarded. Talk to the utility early — it takes time to arrange.
Not sure of the voltage?
Treat it as high voltage and keep well back until the utility confirms it.
What to tell us
- Any wires near the street, the setup spot or the path of the load — photos are best
- Service drops to the house as well as street lines
- Whether you've already spoken to the utility
Sources
WorkSafeBC — OHS Regulation Part 19: Electrical Safety
WorkSafeBC — Working near energized conductors
General information, not legal advice. Rules change — always check the current regulation. Last reviewed October 2026.